Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.
W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Enthalpy and Specific Volume to All Properties
- Enthalpy and Specific Volume to Dry Bulb Temperature Converter
- Enthalpy and Specific Volume to Specific Humidity Converter
- Enthalpy and Specific Volume to Wet Bulb Temperature Converter
- Enthalpy and Specific Volume to Vapour Pressure Converter
- Enthalpy and Specific Volume to Dew Point Temperature Converter