← Main psychrometric calculator

Enthalpy and Specific Volume to Relative Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate relative humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Relative Humidity

— %

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.

    W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Formula for relative humidity

    Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.

    RH = 100 × Pv / Psat(Tdb)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    RH
    Relative humidity, in percent.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    v
    Specific volume (SV), in m³/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Relative Humidity = 45.39 %

    More calculations with these inputs

    Enthalpy and Specific Volume to All Properties