← Main psychrometric calculator
Enthalpy and Specific Volume to Wet Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.
Calculator inputs
Wet Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.
W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Formula for wet bulb temperature
The temperature approached when water evaporates into air adiabatically until the air reaches saturation.
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Wet Bulb Temperature = 18.72 °C
More calculations with these inputs
Enthalpy and Specific Volume to All Properties
- Enthalpy and Specific Volume to Dry Bulb Temperature Converter
- Enthalpy and Specific Volume to Specific Humidity Converter
- Enthalpy and Specific Volume to Relative Humidity Converter
- Enthalpy and Specific Volume to Vapour Pressure Converter
- Enthalpy and Specific Volume to Dew Point Temperature Converter