Enthalpy and Wet Bulb Temperature to Dew Point Temperature Converter

Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Dew Point Temperature

— °C

Calculation history

No calculations saved on this page yet.

    Input calculation

    Apply the wet bulb energy balance to find W and then use the enthalpy to recover the dry bulb temperature. Near 0 °C, small input errors can cause a large change in the result.

    W = Ws + [h − h(Twb, Ws)] / hf(Twb)
    Tdb = (h − 2500 W) / (1.005 + 1.88 W)

    At exactly 0 °C the liquid-water reference gives zero for the enthalpy of the added water. Use a different known property to determine the state.

    Formula for dew point temperature

    The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.

    Psat(Tdp) = Pv

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    Tdp
    Dew point temperature (DP), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.

    Quantity definitions and calculation range

    Worked example

    Enthalpy 52.900253 kJ/kg dry air · Wet Bulb Temperature 18.724547 °C · height 0 m

    Dew Point Temperature = 14.20 °C