← Main psychrometric calculator
Enthalpy and Wet Bulb Temperature to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Apply the wet bulb energy balance to find W and then use the enthalpy to recover the dry bulb temperature. Near 0 °C, small input errors can cause a large change in the result.
W = Ws + [h − h(Twb, Ws)] / hf(Twb)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
At exactly 0 °C the liquid-water reference gives zero for the enthalpy of the added water. Use a different known property to determine the state.
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Wet Bulb Temperature 18.724547 °C · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Enthalpy and Wet Bulb Temperature to All Properties
- Enthalpy and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Enthalpy and Wet Bulb Temperature to Specific Humidity Converter
- Enthalpy and Wet Bulb Temperature to Specific Volume Converter
- Enthalpy and Wet Bulb Temperature to Vapour Pressure Converter
- Enthalpy and Wet Bulb Temperature to Dew Point Temperature Converter