Enthalpy and Wet Bulb Temperature to Specific Volume Converter

Enter the known properties and either total pressure or height above sea level to calculate specific volume.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Volume

— m³/kg dry air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Apply the wet bulb energy balance to find W and then use the enthalpy to recover the dry bulb temperature. Near 0 °C, small input errors can cause a large change in the result.

    W = Ws + [h − h(Twb, Ws)] / hf(Twb)
    Tdb = (h − 2500 W) / (1.005 + 1.88 W)

    At exactly 0 °C the liquid-water reference gives zero for the enthalpy of the added water. Use a different known property to determine the state.

    Formula for specific volume

    Volume occupied by the moist-air mixture per kilogram of dry air.

    v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    v
    Specific volume (SV), in m³/kg dry air.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Enthalpy 52.900253 kJ/kg dry air · Wet Bulb Temperature 18.724547 °C · height 0 m

    Specific Volume = 0.86427 m³/kg dry air