Enthalpy and Wet Bulb Temperature to Specific Volume Converter
Enter the known properties and either total pressure or height above sea level to calculate specific volume.
Calculator inputs
Specific Volume
m³/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Apply the wet bulb energy balance to find W and then use the enthalpy to recover the dry bulb temperature. Near 0 °C, small input errors can cause a large change in the result.
W = Ws + [h − h(Twb, Ws)] / hf(Twb)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
At exactly 0 °C the liquid-water reference gives zero for the enthalpy of the added water. Use a different known property to determine the state.
Formula for specific volume
Volume occupied by the moist-air mixture per kilogram of dry air.
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Wet Bulb Temperature 18.724547 °C · height 0 m
Specific Volume = 0.86427 m³/kg dry air
More calculations with these inputs
Enthalpy and Wet Bulb Temperature to All Properties
- Enthalpy and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Enthalpy and Wet Bulb Temperature to Specific Humidity Converter
- Enthalpy and Wet Bulb Temperature to Relative Humidity Converter
- Enthalpy and Wet Bulb Temperature to Vapour Pressure Converter
- Enthalpy and Wet Bulb Temperature to Dew Point Temperature Converter