← Main psychrometric calculator
Enthalpy and Wet Bulb Temperature to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Apply the wet bulb energy balance to find W and then use the enthalpy to recover the dry bulb temperature. Near 0 °C, small input errors can cause a large change in the result.
W = Ws + [h − h(Twb, Ws)] / hf(Twb)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
At exactly 0 °C the liquid-water reference gives zero for the enthalpy of the added water. Use a different known property to determine the state.
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Wet Bulb Temperature 18.724547 °C · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Enthalpy and Wet Bulb Temperature to All Properties
- Enthalpy and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Enthalpy and Wet Bulb Temperature to Specific Humidity Converter
- Enthalpy and Wet Bulb Temperature to Relative Humidity Converter
- Enthalpy and Wet Bulb Temperature to Specific Volume Converter
- Enthalpy and Wet Bulb Temperature to Dew Point Temperature Converter