← Main psychrometric calculator

Wet Bulb Temperature and Vapour Pressure to All Properties

Calculate the moist-air properties from wet bulb temperature and vapour pressure.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Output properties

PropertyValueUnit
Dry Bulb Temperature DB —°C
Specific Humidity SH —kg water/kg moist air
Relative Humidity RH —%
Enthalpy ET —kJ/kg dry air
Wet Bulb Temperature WB —°C
Specific Volume SV —m³/kg dry air
Vapour Pressure PV —kPa
Dew Point Temperature DP —°C
Total Pressure PT —kPa

Calculation history

No calculations saved on this page yet.

    Input calculation

    Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.

    W = 0.622 × Pv / (P − Pv)
    Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Wet Bulb Temperature 18.724547 °C · Vapour Pressure 1.6191793 kPa · height 0 m

    Enthalpy = 52.90 kJ/kg dry air

    Calculate an individual property