← Main psychrometric calculator
Wet Bulb Temperature and Vapour Pressure to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Vapour Pressure 1.6191793 kPa · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Wet Bulb Temperature and Vapour Pressure to All Properties
- Wet Bulb Temperature and Vapour Pressure to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Vapour Pressure to Specific Humidity Converter
- Wet Bulb Temperature and Vapour Pressure to Enthalpy Converter
- Wet Bulb Temperature and Vapour Pressure to Specific Volume Converter
- Wet Bulb Temperature and Vapour Pressure to Dew Point Temperature Converter