Wet Bulb Temperature and Vapour Pressure to Specific Volume Converter
Enter the known properties and either total pressure or height above sea level to calculate specific volume.
Calculator inputs
Specific Volume
m³/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Formula for specific volume
Volume occupied by the moist-air mixture per kilogram of dry air.
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Vapour Pressure 1.6191793 kPa · height 0 m
Specific Volume = 0.86427 m³/kg dry air
More calculations with these inputs
Wet Bulb Temperature and Vapour Pressure to All Properties
- Wet Bulb Temperature and Vapour Pressure to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Vapour Pressure to Specific Humidity Converter
- Wet Bulb Temperature and Vapour Pressure to Relative Humidity Converter
- Wet Bulb Temperature and Vapour Pressure to Enthalpy Converter