← Main psychrometric calculator

Wet Bulb Temperature and Vapour Pressure to Enthalpy Converter

Enter the known properties and either total pressure or height above sea level to calculate enthalpy.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Enthalpy

— kJ/kg dry air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.

    W = 0.622 × Pv / (P − Pv)
    Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)

    Formula for enthalpy

    Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.

    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Wet Bulb Temperature 18.724547 °C · Vapour Pressure 1.6191793 kPa · height 0 m

    Enthalpy = 52.90 kJ/kg dry air

    More calculations with these inputs

    Wet Bulb Temperature and Vapour Pressure to All Properties