Relative Humidity and Enthalpy to All Properties

Calculate the moist-air properties from relative humidity and enthalpy.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Output properties

PropertyValueUnit
Dry Bulb Temperature DB —°C
Specific Humidity SH —kg water/kg moist air
Relative Humidity RH —%
Enthalpy ET —kJ/kg dry air
Wet Bulb Temperature WB —°C
Specific Volume SV —m³/kg dry air
Vapour Pressure PV —kPa
Dew Point Temperature DP —°C
Total Pressure PT —kPa

Calculation history

No calculations saved on this page yet.

    Input calculation

    Find the dry bulb temperature by matching the supplied enthalpy or specific volume along the constant relative humidity curve.

    Pv = (RH / 100) × Psat(Tdb)
    W = 0.622 × Pv / (P − Pv)
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    RH
    Relative humidity, in percent.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Relative Humidity 45.389339 % · Enthalpy 52.900253 kJ/kg dry air · height 0 m

    Dry Bulb Temperature = 27.00 °C