← Main psychrometric calculator

Relative Humidity and Enthalpy to Specific Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate specific humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Humidity

— kg water/kg moist air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Find the dry bulb temperature by matching the supplied enthalpy or specific volume along the constant relative humidity curve.

    Pv = (RH / 100) × Psat(Tdb)
    W = 0.622 × Pv / (P − Pv)
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Formula for specific humidity

    Mass of water vapour divided by the total mass of moist air.

    q = W / (1 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    RH
    Relative humidity, in percent.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Relative Humidity 45.389339 % · Enthalpy 52.900253 kJ/kg dry air · height 0 m

    Specific Humidity = 0.0100000 kg water/kg moist air

    More calculations with these inputs

    Relative Humidity and Enthalpy to All Properties