Find the dry bulb temperature by matching the supplied enthalpy or specific volume along the constant relative humidity curve.
Pv = (RH / 100) × Psat(Tdb)
W = 0.622 × Pv / (P − Pv)
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Reading dry bulb temperature
Air temperature measured by a dry, shielded thermometer.
The input calculation above gives the dry bulb temperature directly or by solving for it.
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Enthalpy 52.900253 kJ/kg dry air · height 0 m
Dry Bulb Temperature = 27.00 °C
More calculations with these inputs
Relative Humidity and Enthalpy to All Properties
- Relative Humidity and Enthalpy to Specific Humidity Converter
- Relative Humidity and Enthalpy to Wet Bulb Temperature Converter
- Relative Humidity and Enthalpy to Specific Volume Converter
- Relative Humidity and Enthalpy to Vapour Pressure Converter
- Relative Humidity and Enthalpy to Dew Point Temperature Converter