Relative Humidity and Enthalpy to Wet Bulb Temperature Converter

Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Wet Bulb Temperature

— °C

Calculation history

No calculations saved on this page yet.

    Input calculation

    Find the dry bulb temperature by matching the supplied enthalpy or specific volume along the constant relative humidity curve.

    Pv = (RH / 100) × Psat(Tdb)
    W = 0.622 × Pv / (P − Pv)
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Formula for wet bulb temperature

    The temperature approached when water evaporates into air adiabatically until the air reaches saturation.

    h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    RH
    Relative humidity, in percent.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Relative Humidity 45.389339 % · Enthalpy 52.900253 kJ/kg dry air · height 0 m

    Wet Bulb Temperature = 18.72 °C

    More calculations with these inputs

    Relative Humidity and Enthalpy to All Properties